BeerMaster is a long-established cellar cooling brand, originally introduced in 1996 by NRS and later manufactured/distributed by Wolseley Climate Center in the UK. BeerMaster systems are high-performance split coolers often found in pub and brewery cellars. Current models include the BeerMaster Plus range (using R448A refrigerant) and older BeerMaster units (R407C). A BeerMaster setup typically consists of a BMIE indoor evaporator unit and a BMO outdoor unit (the naming BMIE = BeerMaster Internal Evaporator, BMO = BeerMaster Outside unit). Common sizes are often denoted by numbers like BM37, BM48, etc., corresponding to cooling capacity (e.g. ~3.7 kW, 4.8 kW). These units are designed to hold 11–13°C in the cellar continuously (industry standard ~12.7°C). BeerMaster coolers incorporate a digital controller with self-diagnostics and were among the first in cellar cooling to introduce intelligent control and error code displays.
Common Faults: BeerMaster systems share many typical faults with other cellar coolers: condenser fouling or fan failure leading to high head pressure trips, icing due to low charge or evaporator fan issues, and sensor faults. They also have specific error codes on the LED display. For instance, sensor errors are indicated similarly to Wolseley’s standard controllers: P1/OC, P1/SC, P2/OC, P2/SC for air and coil sensor open/short faults (the BeerMaster Plus uses the same convention, as Wolseley’s manual notes). Additionally, BeerMaster glycol chiller variants (if used for beer line cooling) have codes like E1, E2, E6, etc., but for cellar air cooling the main codes of interest are sensor and temperature alarms. The BeerMaster Plus installation manual specifies that if the cellar air temperature deviates by more than –1°C or +2°C from setpoint for 30 minutes, an alarm triggers – useful for alerting of cooling performance issues. High-pressure cut-outs on BeerMasters typically auto-reset after pressure falls ~4 bar below the trip point (trip around ~25 bar on R448A, auto-reset ~21 bar). If the unit repeatedly hits HP trip (compressor cycling on internal thermal cut or HP switch), you likely have a condenser airflow or refrigerant issue. BeerMaster evaporators also have an integral condensate pump and heater options, so pump failures (causing water leaks) or heater faults (for ale conditioning units) can occur.
Error Codes: On BeerMaster cellar coolers, the controller will flash fault codes for probe failures: “P1/OC” (air probe open), “P1/SC” (air probe short), “P2/OC” (defrost/coil probe open), “P2/SC” (coil probe short). These faults latch until power is reset. In normal cooling operation, if the system can’t achieve set temperature, you may see a general alarm (often just an LED or an external alarm output after 30 min out-of-range). Earlier BeerMaster units had a different control panel (BMI controllers) – in some cases, fault codes like E6 have been reported as well. For example, an “E6” error on certain BeerMaster controllers indicated high temperature or communication fault (one tech noted an “E6 comms error” due to a loose connection on a BeerMaster system). Always consult the specific model’s manual, as code definitions may vary slightly with controller version.
Manual: See the BeerMaster Plus Cooling Range Installation & Maintenance Manual (PDF) for official fault code definitions, wiring, and troubleshooting steps. This Wolseley manual covers BeerMaster BMOP (outdoor) and BMIEP (indoor plus) units. It includes an alarm signal guide and maintenance checks.
Common Faults & Troubleshooting (BeerMaster systems):
Issue / Symptom |
Diagnostic Steps |
Technician Fix |
---|---|---|
High Pressure Trip (Compressor stops on HP safety; may show no code, but manual reset might be needed on some units) |
– Signs: The cellar warms up, compressor cycles off, and the outdoor unit may be hot to touch. If equipped, the HP switch might have a popped button (manual reset) or an alarm lamp. Some BeerMasters auto-reset HP after pressure drops, so you might not know except by hearing the compressor cut out after short run. – Check the condenser unit: Is the fan running? A failed condenser fan or motor capacitor will cause rapid pressure rise. Also inspect if the condenser coil is clogged with dust or debris – restricted airflow is a top cause of HP trips. – Verify ambient temperature: a heat wave can push pressures high if the unit is marginal. Ensure any head-pressure control (fan speed regulator) is functioning; some BeerMaster Plus units have fan speed control for noise, but in high ambient it should go full speed. |
– Condenser cleaning: Power-wash or brush the condenser coil to remove dust and lint. Clear airflow around the outdoor unit (no boxes or rubbish blocking intake). – If the condenser fan isn’t running but the compressor is, replace the fan motor or capacitor. Temporarily, you can spray water mist on the coil to bring pressures down, but the real fix is restoring fan operation. – After addressing airflow, reset the HP switch (if manual reset type). On BeerMaster Plus, the HP cut-out resets automatically ~4 bar below trip – you may need to cycle power to restart the compressor if it locked out. – Refrigerant issues: If the condenser is clean and fan OK, yet HP still trips, the system may be overcharged or have non-condensables. A technician should reclaim and recharge to factory spec, especially if service history is unknown. Also ensure no overfeed of refrigerant (check sight glass). – In rare cases, high head pressure can be due to TX valve overfeeding or a blockage causing backed-up liquid. Evaluate subcooling; if very high, recover some charge or check for blockage at the receiver outlet. |
Low Performance / Warm Cellar (Compressor runs continuously but cellar temp stays high; may trigger high-temp alarm after 30+ minutes)) |
– Airflow check: Are the indoor unit’s fans blowing strongly? If BeerMaster has two evaporator fans, ensure both run; the newer BMIEP units have energy-saving modes where only one fan runs off-cycle, but during active cooling both should run full speed. – Temperature difference: Measure cellar air vs. evaporator outlet air. If there’s little to no cooling difference, suspect loss of refrigerant or compressor inefficiency. Check for icing on evaporator or the suction line – could indicate low charge or expansion valve issues. – Look at the unit’s controller display: if it’s flashing an alarm (like “HA” or just alternating temp/alarm), it means temperature hasn’t been achieved. That could result from doors open or excess load, but if the cellar is closed, it’s a mechanical issue. – Inspect evaporator coil for frost/ice buildup. If present primarily on the coil inlet, likely low refrigerant. If whole coil is a block of ice, could be fan failure or very low setpoint (some owners mistakenly set below 8°C – BeerMaster will struggle and ice up). |
– Evaporator fan fixes: If a fan motor is out, replace it. Running on half fans will severely reduce cooling. Also verify the fan speed jumper (some BeerMaster Plus controllers have normal vs. low-noise settings) is in the proper position for full cooling performance. – Defrost the coil: Turn off the compressor (but you can let the evaporator fan run to help thaw). Do not restart until coil fully defrosted. Find cause: if due to low charge, you’ll see pressures very low – have a tech leak-check and recharge the system. If due to low setpoint, remember BeerMasters typically should not be set below ~10°C without a heater kit – adjust setpoint to proper range (11–13°C). – Check expansion valve & filter/drier: A partially blocked TXV or filter can starve the coil causing poor cooling. A tech can check superheat; if abnormally high with warm cellar, likely a restriction – replace the drier and TXV if needed, then vacuum and recharge. – Compressors & valves: If the system pressures are abnormal (e.g. equalized with compressor running, indicating no pumping) and there’s no cooling, the compressor might be internally failed. Confirm by amperage – a significantly low amp draw with no cooling effect could mean broken valves. In that case, compressor replacement is necessary. (Compressors failing is less common; eliminate other causes first.) – Alarm reset: Once the issue is fixed, the high-temp alarm will reset automatically when the cellar cools back down. Some BeerMaster controllers also have an alarm relay that can trigger a beacon or text alert; ensure to clear any latched alarms on the panel by cycling power if needed. |
Unit Icing Up / Low-Pressure Fault (Evaporator coil is freezing, possibly causing compressor off on LP switch if fitted) |
– If equipped, check the LP safety switch: BeerMaster systems often have an LP cut-out to prevent running in a vacuum. If the compressor shuts off after a short run and you see ice, likely LP trip. Confirm by gauge or sight glass: low pressure and/or bubbles indicate under-charge or restriction. – Inspect evaporator fans – again, a non-working fan can cause ice. Also ensure door seals in the cellar are good; high humidity ingress can accelerate frost buildup. – BeerMaster evaporators include a de-ice thermostat (some models) or rely on off-cycle defrost (compressor off intervals). If the controller is set to an extremely low setpoint or continuous run, it might not defrost adequately. Check if the system has a defrost sensor (P2) and if it’s operational – a P2 fault might disable proper defrost logic (the BeerMaster Plus limits minimum setpoint to 8°C if defrost sensor is faulted, to avoid icing). |
– Thaw and Dry: Turn off cooling and let the ice melt. Place towels or ensure drain is clear for water. Do not use hot water on an energized coil. Once clear, turn cooling back on and monitor. – Fix the root cause: For low refrigerant, a certified tech must find the leak, repair, evacuate, and recharge to the correct weight. Given many BeerMaster units ran on R407C (now replaced by R448A in new units), a retrofit might be necessary if a major leak occurred – consult the manual for compatible replacement refrigerants. – If a fan was faulty, replace it and test that both/all evaporator fans operate. – Adjust settings: If icing was due to running too cold, and the cellar doesn’t strictly need <10°C, raise the setpoint. Also ensure the defrost thermostat or cycle timer is working – some BeerMaster controllers rely on the cooling off-cycle to defrost naturally. If icing persists, a timer-controlled off cycle (e.g. 30 minutes off every 6 hours) can be implemented by a tech, or an electric defrost heater kit might be installed for extreme cases (though typically not needed for cellar temps). – LP switch: After correcting cause, reset any tripped LP control if manual (most are auto-reset when pressure rises). If an LP control is overly sensitive or faulty, it could be replaced or its setting adjusted slightly (but only do so within safe limits – usually ~0.2–1.5 bar cut out for R448A, depending on design). |
Controller Fault Code Displayed (Flashing code on BeerMaster display, e.g. P1/OC, P2/SC, or “E” codes in older models) |
– P1 / P2 codes: As with J&E Hall, “P1/OC” means air sensor open circuit, “P1/SC” short circuit. “P2/OC” and “P2/SC” refer to the defrost (evaporator) sensor. If these appear, the controller has detected a failed probe. Check the probe connections at the controller board (loose wires could cause OC/SC errors). Also physically inspect the sensor in the unit – it might have been dislodged or damaged. – Other “E” codes: Some BeerMaster units (especially glycol beer coolers or older digital controllers) have codes like E1, E2, E6. For example, “E1” often denotes a liquid line thermistor fault in glycol systems, “E6” could indicate high temperature cutout. If your BeerMaster panel is showing an “E#” code, refer to the Technician’s Handbook or service manual for that specific model. Wolseley’s provided manuals for BeerMaster Plus primarily use the P1/P2 format for cellar units. – No display / blank controller: If the controller screen is blank or unresponsive, the unit may have no power or a blown internal fuse/transformer. Ensure the unit has power and that the control fuse on the evaporator panel is intact. |
– Sensor Replacement: Swap out the faulty sensor probe with an OEM or compatible sensor (typically NTC thermistors). For BeerMaster, the air sensor and coil sensor are critical – use the same resistance spec. After replacing, reset power to clear the fault code (these faults latch until a reset). Verify the new sensor reads plausibly (the displayed temperature should now be accurate and stable). – Clearing other codes: For any E-code, once the underlying issue is fixed (e.g., replace a thermistor, add glycol if it were a glycol chiller alarm, etc.), you often need to cycle power to reset the error memory. The BeerMaster controller retains error codes until reset to ensure you address them. – Controller repairs: If the display itself is dead, a technician may need to replace the controller board or check its power supply. BeerMaster BMI controllers have separate power boards and display boards – for instance, the BeerMaster BMI power PCB and LED display are replaceable components. If a surge took out the controller, replacing that PCB can revive the unit. – Reconfigure settings: After any controller replacement or prolonged power loss, confirm the setpoints and parameters (fan mode, differential, calibration) match the manual’s recommendations. BeerMaster Plus defaults are documented in the manual (e.g. HP trip at 25 bar, cut-in at 21 bar, temp set around 12°C). Adjust as needed for your cellar’s requirements. |
Technical Notes: BeerMaster units are generally “always on” – they are designed to hold cellar temperature continuously, so avoid turning them off nightly. As the manufacturer notes, switching off a cellar cooler to “save energy” is counterproductive; recovering a warm cellar can take 48 hours and uses more energy while beer may spoil. The evaporator fan should run 24/7 on internal BeerMaster units, circulating air even when not actively cooling – this evens out temperature and helps with humidity control. The BeerMaster Plus models introduced energy-saving fan modes (one fan off-cycle), but continuous circulation is still recommended in critical cooling times. If your BeerMaster has an electric heater kit (for maintaining cask ales ~12°C in winter), ensure the heater’s thermostat is set correctly – a failed heater in a cold ambient could lead to too-cold cellars (LA alarms). Always consult the official manual for wiring any aux heaters or pumps. Lastly, keep an eye (or ear) on the condensate pump (if fitted to the evaporator for draining water). If you hear gurgling or the alarm from the pump, clear any blockage in the drain and verify the pump runs – a stuck condensate pump can cause water leaks in the cellar. BeerMaster manuals will have maintenance sections addressing these auxiliary components.
(Manual Reference: BeerMaster Plus Installation & Maintenance Manual)